Techinical Specification
INPUT SPECIFICATION | ||
Input | Range (°C) | Range (°F) |
J | 0 to 600°C | 32 to 1112°F |
J.1 | 0.0 to 600.0°C | 32.0 to 1112.0°F |
K | 0 to 1200°C | 32 to 2192°F |
K.1 | 0.0 to 950.0°C | 32.0 to 1742.0°F |
PT-100 | -200 to 400°C | -328 to 752°F |
PT.1 | -199.9 to 400.0°C | -199.9 to 752.0°F |
R | 0 to 1600°C | 32 to 2912°F |
S | 0 to 1800°C | 32 to 3272°F |
E | 0 to 650°C | 32 to 1202°F |
N | 0 to 1250°C | 32 to 2282°F |
T | 0 to 350°C | 32 to 662°F |
B | 150 to 1800°C | 302 to 3272°F |
Resolution | J,K,PT-100,R,S,E,N,T,B = 1°C | |
J.1,K.1,PT.1 = 0.1°C | ||
Indication Accuracy | ±0.5% Full Scale ± 1 Digit | |
DISPLAY AND KEYS | ||
Display | Upper: 4 digit, 7 segment, 0.70” | |
Lower: 4 digit, 7 segment, 0.43” | ||
Keys | SET, ENT, INC, DEC | |
CONTROL METHOD | ||
Heating | 1) PID control with Auto-Tuning | |
2) (TP) Time Proportional | ||
3) ON-OFF control | ||
Cooling | 1) BL.TP (Blower Time Proportional) | |
2) ON-OFF control | ||
Alarm | High /Low /Absolute Low/ Inband /Absolute Outband/Outband/End Alarm | |
DIMENSION | ||
Size | 72 (H) x 72 (W) x 85 (D) mm | |
Panel Cutout | 68 (H) x 68 (W) mm | |
POWER SUPPLY | ||
Supply voltage | 24V DC | |
OUTPUT SPECIFICATION | ||
Relay Output | ||
Relay | 2 nos. | |
Relay Type | 1 C/O , (NO-C-NC) | |
Rating | 5A, 230V AC / 28 V DC | |
SSR Drive Output | ||
Output Signal | 12V DC, 30mA DC (ON-OFF Condition) | |
Relay 1 Parallel to SSR | ||
ENVIRONMENT CONDITION | ||
Operating Temp. | 0°C to 55°C | |
Relative Humidity | UP to 95% RH (non-condensing) | |
Protection Level (As per request) | IP-65 (Front side) As per IS/IEC 60529 : 2001 |
Application