Product: PS24-1A
Technical Specification
Input Specification: | |
Supply Voltage | 100 to 270V AC±10%,(L-N) |
Frequency Range | 50/60 Hz |
AC Current (TYP.) | 0.49A@100V AC |
0.24A@270V AC | |
Efficiency (TYP.) | >85%@230VAC |
Start UP time | <1 sec@230VAC & |
<3 sec@100VAC (Full Load) | |
Output Specification: | |
Output Voltage | 24V DC |
Output Current | 1A at 24V |
Ripple & noise | <1% of V out |
Line & Load Regulation | ±1% |
Hold UP Time | <60ms at 230VAC & |
>15ms at 100VAC (Full Load) | |
Protection: | |
Input Fused | 2A-250V AC Internal |
Output Over Load | 110% to 120% of rated output Current protection Protection Type : hiccup mode; |
recover automatically after fault condition is removed | |
Output Short Circuit | Hiccup mode when output is shorted;Recovers automatically after fault condition is removed. |
Over Temperature | Power supply shuts down when the temperature goes above specified limit; |
Turns on automatically after temperature goes back to Normal operating conditions. | |
Physical : | |
Mounting Type | Din Rail Mount |
Size (H) x (W) x (D)(mm) | 90 x 22.5 x 75 |
Material | Polycarbonate (PC) |
Environmental: | |
Working Temperature | -25°C to 50°C * De-rate output power at 3w/°C above +50°C Ambient |
Storage Temperature | -40°C to 85°C |
Relative Humidity | 95% RH Non-condensing |
Warm up time | 5 minutes |
Application
Product Variant
Sr.No | Model Number | Input Voltage | Output Voltage | Current Capacity |
1 | PS24-1A | 100-270V AC | 24V DC | 1A |
2 | PS12-2A | 100-270V AC | 12V DC | 2A |
3 | PS12-1A | 100-270V AC | 12V DC | 1A |
4 | PS24-1.5A | 100-270V AC | 24V DC | 1.5A |