Techinical Specification
Input Types | Input | Range |
J | 0 to 600°C | |
K | 0 to 1200°C | |
PT-100 | -99 to 400°C | |
PT.1 | -99.9 to 400.0°C | |
0-10V DC | -1999 to 9999 | |
0-20mA DC | -1999 to 9999 | |
4-20mA DC | -1999 to 9999 | |
Resolution | J,K,PT-100 = 1°C | |
PT.1 = 0.1°C | ||
0-10V DC,0-20mA DC,4-20mA DC | ||
= 0.1,0.01,0.001,0001 | ||
Indication Accuracy | ±1% of FSD | |
(FSD : full scale deflection) | ||
DISPLAY AND KEYS: | ||
Display | 4 digit,7 seg 0.8” RED or WHITE LED | |
Keys | SET, INC, DEC, ENT | |
DIMENSION: | ||
Size (mm) | 48 (H) x 96 (W) x 76 (D) mm | |
Panel Cutout (mm) | 46 (H) x 92 (W) mm | |
CONTROL METHOD: | ||
Heating | 1. PID Control with Auto-Tuning | |
2. ON-OFF Control | ||
Cooling | 1. BL.TP (Blower Time Proportion) | |
2. ON-OFF Control | ||
Alarm | High/Low/Inband/Outband/ Absolute Low/Absolute Outband | |
OUTPUT SPECIFICATION | ||
Relay Output | ||
Relay | 2 nos. | |
Relay Type | 1 C/O (NO-C-NC) , 2 C/O (NO-C) | |
Rating | 5A, 230V AC/30V DC | |
Analog Output | ||
4 to 20mA DC / 0 to 10 VDC (Factory Set) | ||
Transmitter supply | ||
24V DC | ||
Modbus Communication | ||
RS-485 | ||
AUXILIARY SUPPLY | ||
Supply voltage | 100 to 270V AC, 50-60Hz | |
Power consumption (VA RATING) | Approx 6 VA @ 230V AC MAX | |
ENVIRONMENT CONDITION | ||
Operating Temp. | 0°C to 55°C | |
Relative Humidity | Upto 95% RH | |
(non-condensing) | ||
Protection Level | IP-65 (Front side) As per IS/IEC 60529 : 2001 |
Application
Universal Input (J/K/RTD/4-20mA DC/0-10V DC/0-20mA DC)4-Digit Dual Red/White LED Display2-Relay OutputAnalog Out... Continue
Universal Input (J/K/RTD/4-20mA DC/0-10V DC/0-20mA DC)4-Digit Dual Red/White LED Display2-Relay OutputAnalog Out... Continue